Power Calculator

DC, single-phase AC, three-phase AC, and energy — one power calculator for every circuit.

Calculate

Fields accept plain numbers or formulas like 240/2.

Enter any two values — voltage, current, resistance or power.

Battery or supply voltage.
Current through the load.
Load resistance in ohms.
Power dissipated by the load.
V = 12 V, I = 3 A, R = 4 Ω, P = 36 W
Voltage (V)12.0000 V
Current (I)3.0000 A
Resistance (R)4.0000 Ω
Power (P)36.0000 W

Working

  1. I = V ÷ R = 12 ÷ 4 = 3 A
  2. P = V × I = 12 × 3 = 36 W

How to Use the Power Calculator

Four modes cover the four questions people ask about power. DC power is for batteries, USB supplies and resistive loads: enter any two of voltage, current, resistance and power. Single-phase AC is for household mains: enter any three of voltage, current, power factor and power, and the calculator returns real power (W), apparent power (VA), reactive power (VAR) and the phase angle. Three-phase AC is for motors and industrial loads: the same four values, plus a choice of line-to-line or line-to-neutral voltage. Energy & power answers consumption questions: enter any two of energy, time and average power, and the cost follows from the electricity rate.

All four modes show their working step by step. Results update live as values change — raise the current in the AC panel and watch apparent power climb with it, or stretch the time in the energy panel and watch the cost grow.

DC Power Formulas

DC power is the product of voltage and current: P = V × I. Combined with Ohm’s law (V = I × R), that gives two more forms: P = V² ÷ R and P = I² × R. A 12 V battery driving 3 A through a 4 Ω resistor dissipates 36 W — and all three formulas agree: 12 × 3 = 36, 144 ÷ 4 = 36, 9 × 4 = 36.

P = V × I
P = V² ÷ R
P = I² × R

The squared forms explain two everyday facts. A heater’s power quadruples when its voltage doubles (P = V² ÷ R), which is why the wrong mains voltage destroys appliances. And the heat lost in a cable grows with the square of the current (P = I² × R), which is why power grids transmit at hundreds of kilovolts: high voltage means low current for the same power, and low current means small I²R losses.

Single-Phase AC Power Formulas

In AC circuits, voltage and current are sine waves that may not peak together. The angle between them, φ, decides how much of the apparent power does real work. Real power is P = V × I × cos φ; apparent power is S = V × I; reactive power is Q = V × I × sin φ; and the three form a right triangle, S² = P² + Q². The power factor PF = cos φ = P ÷ S measures the fraction doing work.

P = V × I × PF (watts)
S = V × I (volt-amps)
Q = √(S² − P²) (VAR)
PF = cos φ = P ÷ S

Example: 230 V at 10 A with PF 0.8. P = 230 × 10 × 0.8 = 1,840 W; S = 230 × 10 = 2,300 VA; Q = √(2,300² − 1,840²) = 1,380 VAR; φ = arccos 0.8 = 36.87°. The wiring must carry 10 A and the transformer must supply 2,300 VA even though only 1,840 W does work — the remaining 1,380 VAR shuttles back and forth in the load’s inductance.

Three-Phase Power Formulas

Three-phase power is the workhorse of industry: three voltages 120° apart deliver steady power with smaller conductors than single-phase for the same load. With line-to-line voltage V_LL (between two phases), total power is P = √3 × V_LL × I × PF and apparent power is S = √3 × V_LL × I. With line-to-neutral voltage V_LN (one phase to neutral), the factor becomes 3: P = 3 × V_LN × I × PF. The two agree because V_LL = √3 × V_LN — a 400 V line-to-line system is 231 V line-to-neutral.

P = √3 × V_LL × I × PF
P = 3 × V_LN × I × PF
S = √3 × V_LL × I = 3 × V_LN × I

Example: a motor on 400 V line-to-line drawing 10 A per phase at PF 0.9. P = 1.732 × 400 × 10 × 0.9 = 6,235 W; S = 1.732 × 400 × 10 = 6,928 VA; Q = √(6,928² − 6,235²) = 3,020 VAR. The same motor described with 231 V line-to-neutral gives exactly the same numbers — pick whichever voltage the nameplate or the meter reports.

Energy and Cost: Worked Example

Energy is power sustained over time: E = P × t. A 100 W bulb burning for 2 hours uses E = 100 × 7,200 s = 720,000 J = 0.2 kWh. At $0.15 per kWh that costs $0.03. The same arithmetic scales up: a 2 kW heater running 5 hours a day for 30 days uses 2 × 5 × 30 = 300 kWh, about $45 at $0.15/kWh.

Example — Monthly cost of a heater

A 1,500 W space heater runs 6 hours a day, 30 days a month, at $0.15 per kWh. What does it cost?

Step 1: Energy per day = 1.5 kW × 6 h = 9 kWh.
Step 2: Energy per month = 9 × 30 = 270 kWh.
Step 3: Cost = 270 × $0.15 = $40.50 per month. The energy panel above gives the same answer from power and time, with the rate included.

Common Mistakes

My saved numbers reuse them in any calculator

Save a number once — like your rent or hourly rate — then just type its name instead of the number, in any calculator here. You can also type formulas like 5000 * 1.1 right into any box.

    Saved only in this browser — nothing is sent to us.

    Frequently Asked Questions

    What is the difference between real, apparent and reactive power?

    Real power (P, watts) does the actual work — heat, light, motion. Apparent power (S, volt-amps) is voltage times current, the total power flowing in the circuit. Reactive power (Q, VAR) shuttles back and forth between source and load in inductors and capacitors without doing work. They form a right triangle: S² = P² + Q².

    How is single-phase AC power calculated?

    P = V × I × PF, where PF is the power factor (cos φ). Apparent power is S = V × I and reactive power is Q = √(S² − P²). For example, 230 V at 10 A with PF 0.8 gives P = 1,840 W, S = 2,300 VA and Q = 1,380 VAR.

    How is three-phase power calculated?

    With line-to-line voltage: P = √3 × V_LL × I × PF and S = √3 × V_LL × I. With line-to-neutral voltage: P = 3 × V_LN × I × PF and S = 3 × V_LN × I. The two forms agree for the same system, since V_LL = √3 × V_LN.

    What is power factor?

    Power factor is the ratio of real power to apparent power: PF = P ÷ S = cos φ, where φ is the phase angle between voltage and current. It ranges from 0 to 1. A PF of 1 means all the current does useful work; a PF of 0.8 means 20% of the apparent power is reactive. Low power factor wastes capacity in cables and transformers.

    How is energy related to power?

    Energy is power over time: E = P × t. A 100 W bulb running for 2 hours uses 200 Wh = 0.2 kWh = 720,000 J. Electricity bills charge per kilowatt-hour (kWh), so multiplying kWh by the $/kWh rate gives the cost.

    How many watts is a kilowatt?

    1 kilowatt (kW) = 1,000 watts. 1 kWh is the energy of 1 kW running for 1 hour — 3,600,000 joules. A 2 kW heater running for 30 minutes uses 1 kWh.

    Why does the calculator ask for exactly three AC values?

    Three values determine the fourth through P = V × I × PF: with voltage, current and power factor, power follows; with power, voltage and power factor, current follows. Fewer than three leave the circuit undetermined, and all four can contradict each other — for example a power higher than V × I, which would imply a power factor above 1.

    Related Calculators