Power Factor Calculator
Find power factor, apparent and reactive power — and the capacitor that corrects a lagging load.
Calculate
Fields accept plain numbers or formulas like 240/2.
The correction capacitor is connected in parallel with the load. The calculation assumes an inductive (lagging) load and balanced three-phase loads.
| Power factor (PF) | 0.8696 — fair |
| Phase angle (φ) | 29.59° |
| Real power (P) | 10.0000 kW |
| Apparent power (|S|) | 11.5000 kVA |
| Reactive power (Q) | 5.6789 kVAR |
| Current (I) | 50.0000 A |
| Corrected apparent power | 10.5263 kVA |
| Corrected reactive power | 3.2868 kVAR |
| Capacitor reactive power (Qc) | 2.3921 kVAR |
| Correction capacitor (C) | 143.94 µF (0.000144 F) |
Working
- PF = 1000 × P ÷ (V × I) = 1000 × 10 ÷ (1 × 230 × 50) = 0.8696
- |S| = V × I ÷ 1000 = 11.5 kVA
- Q = √(|S|² − P²) = √(11.5² − 10²) = 5.6789 kVAR
- S_corrected = P ÷ PF_target = 10 ÷ 0.95 = 10.5263 kVA
- Q_corrected = √(S_corrected² − P²) = 3.2868 kVAR
- Qc = Q − Q_corrected = 5.6789 − 3.2868 = 2.3921 kVAR
- C = 1000 × Qc ÷ (2π × f × V²) = 1000 × 2.3921 ÷ (2π × 50 × 230²) = 143.9355 µF
How to Use the Power Factor Calculator
Start with the circuit: single-phase for household and small commercial loads, three-phase line-to-line for industrial motors (400 V class), or three-phase line-to-neutral when the phase voltage is the known value. Then enter the load — real power in kW, voltage in volts, and current in amps — or switch to the known-PF mode and enter the power factor directly instead of the current. Finally set the correction target (0.95 is the usual utility requirement) and the mains frequency. The calculator returns the power factor with a plain-language rating, the apparent and reactive power, and the capacitor size that reaches the target.
All values update live. Raising the target from 0.90 to 0.95 immediately shows the extra capacitance required — and how the required size grows steeply as the target approaches 1.0, which is why correcting all the way to unity is rarely worth it.
Power Factor Formulas
Power factor is the ratio of real power to apparent power: PF = P ÷ S = cos φ, where φ is the phase angle between voltage and current. From measured values it is computed differently per circuit, but the idea is identical — real power divided by voltage times current, with the three-phase factor where it belongs.
The three powers form a right triangle: apparent power is the hypotenuse, real and reactive power the two sides. That triangle is also the whole correction story: raising the power factor means shrinking the reactive side while the real side stays fixed.
Correction Capacitor Formulas
Correcting a lagging load means cancelling part of its reactive power with a capacitor in parallel. First find the apparent power at the target: S_corrected = P ÷ PF_target. Then the reactive power that remains: Q_corrected = √(S_corrected² − P²). The capacitor must supply the difference: Qc = Q − Q_corrected. Finally the capacitance: C = 1000 × Qc ÷ (2π × f × V²) farads for single-phase and three-phase line-to-line, and C = 1000 × Qc ÷ (3 × 2π × f × V_LN²) for three-phase line-to-neutral (one capacitor per phase).
Example: a 10 kW single-phase load at 230 V, 50 A, 50 Hz. PF = 10,000 ÷ 11,500 = 0.87; S = 11.5 kVA; Q = √(11.5² − 10²) = 5.68 kVAR. Correcting to 0.95: S_corrected = 10 ÷ 0.95 = 10.53 kVA; Q_corrected = √(10.53² − 10²) = 3.29 kVAR; Qc = 5.68 − 3.29 = 2.39 kVAR; C = 1000 × 2.39 ÷ (2π × 50 × 230²) = 143.9 µF.
What Counts as a Good Power Factor
| Power factor | Rating | What it means |
|---|---|---|
| 0.95 – 1.00 | Excellent | Meets almost every utility requirement; no penalty, minimal wasted capacity. |
| 0.90 – 0.95 | Good | Acceptable for most loads; correction pays only for large installations. |
| 0.80 – 0.90 | Fair | Worth correcting for motors and large loads; some utilities start charging here. |
| 0.70 – 0.80 | Poor | About a quarter of the current does no work; correction usually pays back quickly. |
| Below 0.70 | Very poor | Severely oversized cables and transformers; correction is urgent for large loads. |
Many utilities bill a penalty or require correction below 0.90 or 0.95, and some charge for reactive energy (kVARh) directly. The threshold varies by tariff, so the bill — not a rule of thumb — decides whether correction pays.
What Causes a Low Power Factor
Almost every low power factor traces back to inductance. Induction motors are the biggest contributor: a lightly loaded motor can run at PF 0.7 or worse, because the magnetizing current stays nearly constant while the real power falls with the load. Transformers draw magnetizing current even at no load. Fluorescent and discharge lamps with magnetic ballasts, induction furnaces and welding equipment add more. Electronic loads are a separate case: rectifiers and switched-mode supplies draw current in short pulses, creating distortion power factor that capacitors alone cannot fix — that needs harmonic filtering, not just capacitance.
Correcting with capacitors has limits. A fixed capacitor corrects one load level; if the load varies, the correction is wrong half the time. Over-correction pushes the power factor leading, which raises the voltage and can resonate with the supply inductance. Large installations therefore use switched capacitor banks that step in and out with the load, or synchronous condensers for the largest sites.
Common Mistakes
- Sizing the capacitor from kW instead of kVAR. The capacitor cancels reactive power, not real power. The required Qc comes from the power triangle (Q − Q_corrected), not from the load’s wattage.
- Correcting to exactly 1.0. The last few percent of correction need the most capacitance and risk over-correction when the load drops. A 0.95 target captures most of the benefit at a fraction of the size.
- Using line-to-line voltage in the line-to-neutral formula. The capacitor formula squares the voltage, so a √3 mix-up changes the capacitance by a factor of 3.
- Forgetting the capacitor stays charged. A power-factor capacitor holds a lethal charge after disconnection. Discharge resistors and proper lockout are part of the installation, not an afterthought.
- Expecting capacitors to fix harmonic distortion. Capacitors correct displacement power factor (the phase shift). Distortion from non-linear loads needs filters or active correction — and plain capacitors can make harmonics worse through resonance.
- Reading PF from a meter that measures only displacement. Cheap meters assume sine waves. With distorted waveforms the true power factor (real power ÷ apparent power) is lower than cos φ alone suggests.
My saved numbers reuse them in any calculator
Save a number once — like your rent or hourly rate — then just type its name instead of the number, in any calculator here. You can also type formulas like 5000 * 1.1 right into any box.
Saved only in this browser — nothing is sent to us.
Frequently Asked Questions
What is power factor?
Power factor is the ratio of real power to apparent power: PF = P ÷ S = cos φ. It is 1 when voltage and current are in phase and drops toward 0 as they drift apart. A PF of 0.8 means 80% of the apparent power does useful work and 20% is reactive.
How is power factor calculated from voltage, current and power?
Single-phase: PF = 1000 × P(kW) ÷ (V × I). Three-phase line-to-line: PF = 1000 × P(kW) ÷ (√3 × V_LL × I). Three-phase line-to-neutral: PF = 1000 × P(kW) ÷ (3 × V_LN × I). For example, 10 kW at 230 V and 50 A single-phase gives PF = 10,000 ÷ 11,500 = 0.87.
What is a good power factor?
Above 0.95 is excellent and usually avoids utility penalties; 0.90–0.95 is good; 0.80–0.90 is fair and worth improving for large loads; below 0.80 is poor; below 0.70 is very poor. Many utilities charge extra or require correction when the power factor falls below 0.90 or 0.95.
What causes a low power factor?
Inductive loads — motors, transformers, fluorescent and discharge lighting, induction furnaces. Inductors make current lag voltage, creating reactive power that flows back and forth without doing work. The wiring still has to carry that extra current, so cables, transformers and generators are loaded more heavily than the real power alone would suggest.
How does a capacitor correct power factor?
A capacitor draws leading reactive power that cancels the lagging reactive power of an inductive load. The capacitor is connected in parallel with the load. The required capacitance is C = 1000 × Qc ÷ (2π × f × V²) farads, where Qc is the reactive power to cancel in kVAR, f is the frequency in Hz and V is the voltage. For three-phase line-to-neutral, the denominator gains a factor of 3.
What is the difference between leading and lagging power factor?
Lagging means current lags voltage (inductive load — the common case). Leading means current leads voltage (capacitive load, or an over-corrected inductive load). This calculator assumes an inductive load and does not distinguish the two: the PF value is |cos φ| in both cases.
Why size the capacitor for a target of 0.95 instead of 1.0?
Correcting to exactly 1.0 needs a large capacitor and risks over-correction — if the load drops, the capacitor dominates and the power factor goes leading, which can raise voltage and cause resonance with the supply inductance. A target of 0.95 captures most of the benefit (about 70–80% of the reactive power) at a fraction of the cost.
What is the difference between kW, kVA and kVAR?
kW is real power — the work done. kVA is apparent power — voltage times current. kVAR is reactive power — the power that oscillates without doing work. They form a right triangle: (kVA)² = (kW)² + (kVAR)². A 10 kW load at PF 0.8 draws 12.5 kVA and 7.5 kVAR.