Voltage Drop Calculator
Long wire runs lose voltage before the power arrives. Enter the wire size, material, one-way length, voltage and current, and see the drop in volts and percent, the voltage left at the load, and whether the run stays within the 3% guideline — for DC, single-phase and three-phase circuits.
Check Voltage Drop on a Wire Run
Enter the wire and the load — the drop in volts and percent updates live, with the voltage left at the load and the 3% guideline verdict. Fields accept plain numbers or formulas like 150/2.
Circuit type
Wire
Copper is the standard for building wire. Aluminum drops about 64% more voltage at the same gauge.
In ohm-meters, scientific notation is fine: copper is 1.72×10⁻⁸ Ω·m, so type 1.72e-8.
Bigger number, thinner wire: 12 AWG is standard for a 20-amp household circuit, 14 AWG for 15-amp.
Measure the route the cable actually takes, including bends and vertical runs.
Resistance is shown per 1000 ft for feet, per km for meters.
Load
120 V or 240 V for household mains, 12 V or 48 V for low-voltage DC, 480 V for three-phase.
The running current in amps — from the nameplate, or watts divided by volts for a resistive load.
Above the 5% combined limit — the guideline is 3% on a branch circuit, 5% combined.
Drop breakdown
| Wire | 12 AWG Copper |
| Resistance per 1000 ft | 1.5844 Ω/kft |
| Resistance per km | 5.1983 Ω/km |
| Wire (loop) resistance | 0.3169 Ω |
| Voltage drop | 6.34 V |
| Percentage drop | 5.28% |
| Voltage at the load | 113.66 V |
| Longest run within 3% | 56.8 ft |
| Gauge that meets 3% at this length | 9 AWG |
Sizing notes
- The drop is over the 5% combined limit — motors will run hot, lights will dim and electronics may misbehave. Switch to 9 AWG (or thicker) to bring this run within 3%, or shorten the run to 56.8 ft.
- Values assume solid round conductors at 20 °C (68 °F). Hot wire has higher resistance, so a run near the limit in summer can cross it.
Results copied to your clipboard.
How Voltage Drop Works
Every wire resists current a little, and that resistance turns a small part of the energy into heat along the way. The voltage at the far end is therefore lower than the voltage at the source — the difference is the voltage drop. It is found from Ohm's law applied to the wire itself: drop = current × wire resistance, and the wire resistance is the length times the resistance per unit length of the gauge and material. Two formulas cover every case. For DC and single-phase AC the current makes a round trip — out on one conductor and back on the other — so the drop is V = I × 2 × L × R ÷ 1000, with L the one-way length in feet and R the resistance per 1000 feet (or L in meters and R per kilometer). For three-phase AC the balanced currents partly cancel in the shared return, and the line-to-line drop is V = √3 × I × L × R ÷ 1000 — about 1.732 instead of 2, on one length. The percentage drop is the drop divided by the supply voltage, times 100, and the voltage at the load is simply the supply voltage minus the drop.
The resistance per length comes from the wire gauge table: 12 AWG copper is 1.5844 ohms per 1000 ft (5.1983 ohms per km) at 20 °C, 10 AWG copper is 0.9965 ohms per 1000 ft, and 8 AWG is 0.6266. Aluminum of the same gauge is about 64% higher. Resistance rises with temperature, so a run that passes on a cool morning can fail on a hot afternoon — the values here are for 20 °C (68 °F), and real installations should allow margin for heat.
Worked Example: 100 Feet of 12 AWG at 20 Amps
Take a standard household branch circuit: copper 12 AWG, a 100-foot one-way run, 120 V supply, 20 A load, single phase. Step by step: the resistance per 1000 ft of 12 AWG copper is 1.5844 ohms, so the loop resistance for 200 feet of wire (out and back) is 2 × 100 × 1.5844 ÷ 1000 = 0.3169 ohms. The drop is 20 A × 0.3169 Ω = 6.34 V. As a percentage of 120 V that is 6.34 ÷ 120 × 100 = 5.28%, leaving 113.66 V at the load. That fails both guidelines: the 3% branch-circuit limit is 3.6 V, and even the 5% combined limit is 6 V. The longest run that stays within 3% at 20 A is (0.03 × 120 × 1000) ÷ (2 × 20 × 1.5844) = 56.80 feet — barely past halfway. The fix is thicker wire: 9 AWG copper drops only 2.63% on the same run, so the calculator recommends 9 AWG as the smallest gauge that meets the 3% rule here.
The 3% and 5% Rules
Electrical codes recommend keeping the drop to 3% or less on a branch circuit — the run from the breaker to the outlet — and 5% or less for the feeder and the branch circuit combined. The limits are recommendations for efficiency and equipment performance, and most designers and inspectors treat them as the standard to meet. In volts, the limits are easy to remember because they scale with the supply voltage.
| Supply voltage | 3% limit | 5% limit | Typical use |
|---|---|---|---|
| 12 V | 0.36 V | 0.60 V | Landscape lighting, RV, automotive |
| 24 V | 0.72 V | 1.20 V | HVAC controls, landscape lighting |
| 48 V | 1.44 V | 2.40 V | Solar, battery, telecom |
| 120 V | 3.60 V | 6.00 V | Household branch circuits |
| 240 V | 7.20 V | 12.00 V | Large appliances, subpanels |
| 480 V | 14.40 V | 24.00 V | Three-phase commercial |
The table shows why low-voltage systems are so unforgiving: at 12 V the whole 3% budget is 0.36 V, so a drop that is invisible at 120 V can cripple a 12 V run. The same table shows why higher voltage helps — doubling the voltage doubles the allowed drop in volts, and for the same power it quarters the percentage drop, because the current halves as well.
Worked Example: Three-Phase 480 V
Three-phase runs behave differently, and usually better. Take a 10 AWG copper run, 150 feet one way, 480 V three-phase, 30 A. The resistance per 1000 ft of 10 AWG copper is 0.9965 ohms. The drop is √3 × 30 × 150 × 0.9965 ÷ 1000 = 1.732 × 30 × 150 × 0.9965 ÷ 1000 = 7.77 V. As a percentage of 480 V that is 7.77 ÷ 480 × 100 = 1.62%, leaving 472.23 V at the load — comfortably inside the 3% limit of 14.4 V. The same current on the same wire at 120 V single phase would drop 8.97 V, or 7.47%: the higher voltage and the √3 factor together make the difference. That is one reason long commercial runs are three-phase at 480 V rather than single-phase at 120 V.
What to Do When the Drop Is Too High
Four fixes exist, and upsizing the wire is usually the first. Each step of 3 AWG gauges halves the resistance, so the drop falls fast: going from 12 AWG to 10 AWG copper cuts the resistance by about 37%, and to 8 AWG by about 60%. The calculator names the smallest gauge that brings the run within 3% — use that, or go one thicker still for margin. The second fix is a shorter run: reroute the cable, or move the subpanel closer to the load. The third is less current on the run: split the load across two circuits, so each carries half the current and half the drop. The fourth is a higher supply voltage, which is why a 240 V feed beats a 120 V feed for the same power. What does not help is a bigger breaker — the breaker protects against overload, not against drop, and a run with excessive drop is usually already running its equipment below rated voltage, which makes motors draw more current and run hotter.
Low-Voltage DC: Where Drop Bites Hardest
Low-voltage DC deserves its own warning, because the arithmetic is merciless. Take a 48 V solar run: aluminum 6 AWG, 50 meters one way, 15 A. The resistance per km of 6 AWG aluminum is 2.1200 ohms, so the drop is 2 × 15 × 50 × 2.1200 ÷ 1000 = 3.18 V — 6.63% of 48 V, over even the 5% limit. The same run in copper 6 AWG drops 1.94 V (4.04%), still over 3%; copper 4 AWG drops 1.22 V (2.54%) and passes. The lesson is that low-voltage runs need wire far thicker than the current alone suggests, and aluminum needs two gauges larger than copper for the same job. For landscape lighting and solar, the right answer is often to run the power at a higher voltage and step it down at the load, rather than to keep buying thicker copper.
Common Voltage Drop Mistakes
The most common mistake is entering the round-trip length instead of the one-way length — the calculator already doubles it for DC and single-phase, so a round-trip entry makes the answer twice as large as it should be. The second is using the breaker rating instead of the actual load current: a 20-amp circuit carrying 8 amps drops less than half as much as the breaker figure suggests. The third is forgetting temperature — copper resistance rises about 0.4% per degree Celsius, so wire in a hot attic at 60 °C has about 16% more resistance than at 20 °C. The fourth is mixing up aluminum and copper, or using a gauge table for one material with the other. The fifth is ignoring power factor on AC motor loads: the formulas here assume the current and voltage are in step, and a motor with a low power factor draws more current for the same watts, which raises the real drop. When the load is a motor, use the nameplate full-load amps, not watts divided by volts.
My saved numbers reuse them in any calculator
Save a number once — like your rent or hourly rate — then just type its name instead of the number, in any calculator here. You can also type formulas like 5000 * 1.1 right into any box.
Saved only in this browser — nothing is sent to us.
Frequently Asked Questions
What is voltage drop?
Voltage drop is the voltage lost along a wire because the wire itself has resistance. Current flowing through that resistance turns a small part of the energy into heat, so the voltage at the far end is lower than the voltage at the source. The drop grows with current, with length, and with thinner wire — double any of those and the drop roughly doubles. A small drop is normal; a large one makes motors run hot, lights dim and electronics misbehave.
Why is the length doubled for DC and single-phase, but not for three-phase?
In a DC or single-phase circuit the current travels out along one conductor and back along the other, so the total wire in the path is twice the one-way length — that is the factor of 2 in the formula. In a balanced three-phase circuit the three currents partly cancel in the shared return path, and the line-to-line drop works out to the square root of 3 (about 1.732) times the one-way length instead. Enter the one-way length in both cases and the calculator applies the right factor.
What is the 3% voltage drop rule?
Electrical codes recommend keeping the drop to 3% or less on a branch circuit (the run from the breaker to the outlet) and 5% or less for the feeder plus the branch circuit combined. At 120 V, 3% is 3.6 V — so a load should still see at least 116.4 V. The rule is a recommendation for efficiency and equipment performance, not a hard pass/fail in every jurisdiction, but inspectors and designers treat it as the standard to meet.
How do I fix a voltage drop that is too high?
Use thicker wire — it has less resistance per foot, so the drop falls. Going from 12 AWG to 10 AWG copper cuts the resistance by about 37%, and to 8 AWG by about 60%. The calculator names the smallest gauge that brings the run within 3% for your length and current. The other fixes are a shorter run, a lower current (split the load across two circuits), or a higher supply voltage — doubling the voltage quarters the percentage drop for the same power.
Does the wire material matter?
Yes. Aluminum has about 64% higher resistivity than copper (2.82 vs 1.72 × 10⁻⁸ ohm-m), so an aluminum conductor drops about 64% more voltage than the same gauge of copper. That is why aluminum runs are usually sized two gauges larger than copper for the same job. Silver and gold conduct slightly better than copper but are never used for building wire; nichrome and steel are far worse and are used for heating elements, not power runs.
Does voltage drop matter for DC circuits?
Often more than for AC. Low-voltage DC systems — 12 V or 48 V solar, battery and landscape-lighting runs — have almost no voltage to spare: a 3.6 V drop that is a minor 3% at 120 V is a crippling 30% at 12 V. The same formula applies, with the factor of 2 for the out-and-back run. Low-voltage runs need much thicker wire than the current alone would suggest, or the load simply does not get enough voltage to work.
Should I enter the one-way length or the round-trip length?
One-way — the distance from the source to the load along the wire. The calculator doubles it internally for DC and single-phase circuits, because the current makes the round trip. If you enter the round-trip length by mistake, the answer comes out twice as large as it should be. Measure the route the cable actually takes, including bends and vertical drops, not the straight-line distance on a plan.