Wire Gauge Calculator

Pick any American Wire Gauge size from 4/0 down to 40 and see the diameter, cross-sectional area and resistance for copper, aluminum and six more materials — or enter a measured diameter and find the nearest AWG size. The full chart is on the page.

Look Up Any AWG Wire Size

Pick a gauge and a material — diameter, area and resistance update live. Or measure a bare conductor and find its gauge. Fields accept plain numbers or formulas like 2.5+0.1.

Lookup mode

Wire

Bigger number, thinner wire: 12 AWG is standard for a 20-amp household circuit, 14 AWG for 15-amp.

Copper is the reference. Aluminum has about 64% more resistance at the same gauge.

The resistance of one conductor of this length — useful for voltage-drop checks.

Resistance is shown per 1000 ft and per km either way.

12 AWG Copper wire is 2.0525 mm in diameter with a cross-section of 3.3088 mm² and a resistance of 5.1983 ohms per kilometer at 20 °C.
2.0525 mm diameter

Size and resistance — 12 AWG Copper

Diameter0.0808 in
Diameter2.0525 mm
Cross-sectional area6.5299 kcmil
Cross-sectional area0.0051 in²
Cross-sectional area3.3088 mm²
Resistance per 1000 ft1.5844 Ω/kft
Resistance per km5.1983 Ω/km
Resistivity at 20 °C1.72E-8 Ω·m
Total resistance of 100 ft (one conductor)0.1584 Ω

AWG chart — Copper at 20 °C

Diameter and area exclude insulation. Resistance is per 1000 ft and per km for the material selected above. The selected gauge is highlighted.

AWG #Diameter (in)Diameter (mm)Area (kcmil)Area (mm²)Ω / kftΩ / km
0000 (4/0) 0.4600 11.6840 211.6000 107.2193 0.0489 0.1604
000 (3/0) 0.4096 10.4049 167.8064 85.0288 0.0617 0.2023
00 (2/0) 0.3648 9.2658 133.0765 67.4309 0.0777 0.2551
0 (1/0) 0.3249 8.2515 105.5345 53.4751 0.0980 0.3216
1 0.2893 7.3481 83.6927 42.4077 0.1236 0.4056
2 0.2576 6.5437 66.3713 33.6308 0.1559 0.5114
3 0.2294 5.8273 52.6348 26.6705 0.1966 0.6449
4 0.2043 5.1894 41.7413 21.1506 0.2479 0.8132
5 0.1819 4.6213 33.1024 16.7732 0.3126 1.0254
6 0.1620 4.1154 26.2514 13.3018 0.3941 1.2931
7 0.1443 3.6649 20.8183 10.5488 0.4970 1.6305
8 0.1285 3.2636 16.5097 8.3656 0.6267 2.0560
9 0.1144 2.9064 13.0927 6.6342 0.7902 2.5926
10 0.1019 2.5882 10.3830 5.2612 0.9965 3.2692
11 0.0907 2.3048 8.2341 4.1723 1.2565 4.1224
12 0.0808 2.0525 6.5299 3.3088 1.5844 5.1983
13 0.0720 1.8278 5.1785 2.6240 1.9979 6.5549
14 0.0641 1.6277 4.1067 2.0809 2.5194 8.2656
15 0.0571 1.4495 3.2568 1.6502 3.1769 10.4228
16 0.0508 1.2908 2.5827 1.3087 4.0059 13.1429
17 0.0453 1.1495 2.0482 1.0378 5.0514 16.5728
18 0.0403 1.0237 1.6243 0.8230 6.3697 20.8980
19 0.0359 0.9116 1.2881 0.6527 8.0320 26.3518
20 0.0320 0.8118 1.0215 0.5176 10.1282 33.2291
21 0.0285 0.7229 0.8101 0.4105 12.7714 41.9011
22 0.0253 0.6438 0.6424 0.3255 16.1045 52.8363
23 0.0226 0.5733 0.5095 0.2582 20.3074 66.6253
24 0.0201 0.5106 0.4040 0.2047 25.6072 84.0130
25 0.0179 0.4547 0.3204 0.1624 32.2900 105.9384
26 0.0159 0.4049 0.2541 0.1288 40.7170 133.5858
27 0.0142 0.3606 0.2015 0.1021 51.3431 168.4486
28 0.0126 0.3211 0.1598 0.0810 64.7425 212.4098
29 0.0113 0.2859 0.1267 0.0642 81.6388 267.8438
30 0.0100 0.2546 0.1005 0.0509 102.9446 337.7448
31 0.0089 0.2268 0.0797 0.0404 129.8108 425.8884
32 0.0080 0.2019 0.0632 0.0320 163.6884 537.0353
33 0.0071 0.1798 0.0501 0.0254 206.4072 677.1890
34 0.0063 0.1601 0.0398 0.0201 260.2747 853.9196
35 0.0056 0.1426 0.0315 0.0160 328.2003 1,076.7727
36 0.0050 0.1270 0.0250 0.0127 413.8530 1,357.7854
37 0.0045 0.1131 0.0198 0.0100 521.8590 1,712.1357
38 0.0040 0.1007 0.0157 0.0080 658.0520 2,158.9633
39 0.0035 0.0897 0.0125 0.0063 829.7883 2,722.4025
40 0.0031 0.0799 0.0099 0.0050 1,046.3437 3,432.8861

How AWG Wire Sizes Work

American Wire Gauge — AWG, also called Brown & Sharpe gauge — is the standard system for wire sizes in North America, in use since 1857 and fixed by the ASTM B 258 standard. It covers solid, round, nonferrous conductors, with sizes running from 4/0 (the thickest, about 11.68 mm across) down to 40 (the thinnest, about 0.08 mm). The numbering runs backwards: a bigger number means a thinner wire. 4/0 is written as 0000, then 000 (3/0), 00 (2/0), 0 (1/0), and then 1, 2, 3 and so on down to 40. The number originally counted how many times the wire had been pulled through the drawing dies — each pull made it thinner, so more pulls meant a higher number and a smaller wire.

Every size follows one formula. The diameter in inches is 0.005 × 92^((36 − n) ÷ 39), where n is the gauge number (4/0 counts as −3, 3/0 as −2, 2/0 as −1, 1/0 as 0). In millimeters the same formula starts from 0.127 instead of 0.005. The cross-sectional area follows from the diameter: area in kcmil is 1,000 times the diameter in inches squared, area in square inches is (π ÷ 4) times the diameter squared, and area in square millimeters is (π ÷ 4) times the diameter in millimeters squared. Resistance follows from the area and the material: resistance per kilometer is 10^9 × resistivity ÷ area in mm², and resistance per 1000 feet is the per-km figure times 0.3048. The pattern is geometric: each step of 3 gauges halves or doubles the area, and each step of 6 gauges halves or doubles the diameter — so 9 AWG has about twice the area of 12 AWG, and 6 AWG has about twice the diameter.

Worked Example: 12 AWG Copper

Take the most common household size, 12 AWG copper, with a 100-foot length entered. Step by step: the diameter is 0.005 × 92^((36 − 12) ÷ 39) = 0.005 × 92^(24 ÷ 39) = 0.0808 inches, or 2.0525 mm. The area in kcmil is 1,000 × 0.0808² = 6.5299 kcmil; in square inches it is (π ÷ 4) × 0.0808² = 0.0051 in², and in square millimeters it is (π ÷ 4) × 2.0525² = 3.3088 mm². The resistance per kilometer is 10^9 × 1.72 × 10⁻⁸ ÷ 3.3088 = 5.1983 ohms per km, and per 1000 feet it is 5.1983 × 0.3048 = 1.5844 ohms per kft. A 100-foot conductor of this wire has a total resistance of 5.1983 × 30.48 ÷ 1000 = 0.1584 ohms. Every figure in the chart below is produced by the same chain of formulas — pick any gauge and the same steps give its row.

Worked Example: 2 AWG Copper, and What the Material Does

A heavier example shows the scale. 2 AWG copper measures 0.2576 inches (6.5437 mm) across, with an area of 66.3713 kcmil (33.6308 mm²) and a resistance of 0.1559 ohms per 1000 ft (0.5114 ohms per km) — about a tenth of the resistance of 12 AWG, because the area is about ten times larger. The material matters just as much as the size. For 12 AWG, the resistance per 1000 ft by material is:

MaterialResistivity (Ω·m)Ω / 1000 ftΩ / km
Silver1.59 × 10⁻⁸1.46474.8054
Copper1.72 × 10⁻⁸1.58445.1983
Gold2.44 × 10⁻⁸2.24777.3743
Aluminum2.82 × 10⁻⁸2.59778.5228
Nickel6.99 × 10⁻⁸6.439121.1257
Carbon steel1.43 × 10⁻⁷13.173043.2184
Electrical steel4.60 × 10⁻⁷42.3746139.0244
Nichrome1.10 × 10⁻⁶101.3306332.4495

Silver beats copper slightly and gold is close, but neither is used for building wire. Aluminum is about 64% worse than copper, which is why aluminum runs are usually sized two gauges larger. Nichrome is about 64 times worse than copper — exactly why it is used for heater elements, where resistance is the point, and copper is used for power wire, where it is the problem. All values are at 20 °C (68 °F); resistance rises with temperature.

Finding a Gauge from a Measured Diameter

When the wire is already in hand and the gauge is unknown, the formula runs backwards. Measure the stripped conductor with calipers — bare metal only, never over the insulation — in millimeters, in two or three places, and average the readings. The gauge is n = 36 − 39 × log(d ÷ 0.005) ÷ log(92), with d the diameter in inches. A conductor measuring 2.0525 mm is exactly 12 AWG; a conductor measuring 3.00 mm gives an exact gauge of 9.30, so the nearest standard size is 9 AWG (2.9064 mm). If the measured diameter sits halfway between two sizes, the wire is usually the thicker of the two — manufacturing tolerance and a slightly oval cross-section both push measurements up, not down. Switch the calculator above to diameter lookup and it does the inversion for you, including the exact gauge figure.

Choosing a Gauge for a Job

Gauge is chosen by current and by length together, not by current alone. The ampacity tables in the electrical code set the maximum current for each gauge at a given insulation temperature — 12 AWG copper is the usual choice for a 20-amp household circuit, 14 AWG for 15-amp, 10 AWG for 30-amp — but a long run can need thicker wire than the ampacity table suggests, because voltage drop grows with length while ampacity does not. A 20-amp load 100 feet away on 12 AWG drops 5.28%, over the 3% guideline, even though the wire is perfectly safe at 20 amps; 9 AWG fixes the drop. The wire gauge calculator above gives the size, the voltage drop calculator prices the run, and the two together give the right answer: first pick the gauge the current allows, then check the drop and go thicker if the run is long.

Stranded Wire, Insulation and Temperature

Three details keep the table honest. First, the table is for a single solid round conductor, and the AWG size of a stranded wire is set by the total cross-sectional area of all its strands — so a stranded 12 AWG has the same area and nearly the same DC resistance as a solid 12 AWG, with a small penalty in practice because the bundle is not a perfect circle. Second, diameter and area exclude the insulation, which can add a millimeter or more — measuring over the jacket lands several gauges off. Third, all resistances are at 20 °C: copper resistance rises about 0.4% per degree Celsius, so wire in a hot attic runs measurably higher than the table says. For sizing work, treat the table as the starting point and the electrical code as the authority.

My saved numbers reuse them in any calculator

Save a number once — like your rent or hourly rate — then just type its name instead of the number, in any calculator here. You can also type formulas like 5000 * 1.1 right into any box.

    Saved only in this browser — nothing is sent to us.

    Reference values for solid round conductors at 20 °C (68 °F); diameter and area exclude insulation. Real wire differs with stranding, temperature and manufacturing tolerance. Always verify wire size against the National Electrical Code and local rules before installing.

    Frequently Asked Questions

    What is AWG?

    AWG — American Wire Gauge, also called Brown & Sharpe gauge — is the standard system for wire sizes in North America, in use since 1857. It covers solid, round, nonferrous conductors, with sizes running from 4/0 (the thickest, about 11.68 mm across) down to 40 (the thinnest, about 0.08 mm). The dimensions are fixed by the ASTM B 258 standard, so a 12 AWG wire is the same diameter whoever makes it.

    Does a bigger AWG number mean a bigger wire?

    The opposite: a bigger number means a thinner wire. 4/0 is the thickest common size, 0 (1/0) is thinner than 00 (2/0), and 40 gauge is hair-thin. Each step of 3 gauges halves or doubles the cross-sectional area, and each step of 6 gauges halves or doubles the diameter. So 9 AWG has about twice the area of 12 AWG, and 6 AWG has about twice the diameter of 12 AWG. The backward numbering comes from the old wire-drawing process — the number counted how many times the wire had been pulled through the dies.

    How is the wire diameter calculated from the gauge?

    With one formula: diameter in inches = 0.005 × 92^((36 − n) / 39), where n is the gauge number (4/0 counts as −3, 3/0 as −2, 2/0 as −1, 1/0 as 0). For 12 AWG that gives 0.005 × 92^(24/39) = 0.0808 inches, or 2.0525 mm. The area follows from the diameter — area in kcmil is 1,000 times the diameter in inches squared, and area in mm² is (π/4) times the diameter in mm squared.

    What is a kcmil?

    A kcmil — kilo-circular mil — is the traditional unit for large wire areas in North America. One circular mil is the area of a circle 0.001 inches across, and a kcmil is 1,000 of those. A 4/0 conductor is 211.6 kcmil; a 12 AWG conductor is 6.53 kcmil. Because area scales with the square of the diameter, kcmil is a convenient way to compare sizes: doubling the kcmil doubles the current the wire can carry for the same heating.

    Why does resistance change with the material?

    Every metal resists current differently — that property is its resistivity. Copper is the reference at 1.72 × 10⁻⁸ ohm-m; aluminum is about 64% higher at 2.82 × 10⁻⁸, so the same gauge of aluminum has 64% more resistance. Silver (1.59) and gold (2.44) are slightly better or close to copper, nickel (6.99) is about four times worse, and nichrome (110) is about sixty-four times worse — which is exactly why nichrome is used for heater wire and copper is used for power wire.

    Do the numbers apply to stranded wire?

    Approximately. The table is for a single solid round conductor, and the AWG size of a stranded wire is set by the total cross-sectional area of all its strands — so a stranded 12 AWG has the same area and nearly the same DC resistance as a solid 12 AWG. In practice stranded wire measures a touch higher in resistance (the strands are slightly compressed and the bundle is not a perfect circle), and at high frequencies the skin effect pushes current to the outside, raising AC resistance. For ordinary mains wiring the table values are close enough.

    How do I measure a wire to find its gauge?

    Strip the insulation and measure the bare conductor with calipers — in millimeters is easiest. Measure in two or three places and take the average, since wire is rarely perfectly round. Then enter the diameter in the reverse lookup above: the calculator inverts the diameter formula and names the nearest AWG size. Do not measure over the insulation — that adds a millimeter or more and lands you several gauges off.