SWG to mm Calculator
Pick any Standard Wire Gauge size from 7/0 down to 50 and see the diameter, area and copper resistance — or enter a measured diameter and find the nearest SWG size. The full BS 3737 chart is on the page.
Convert SWG to mm
| SWG size | 12 SWG |
| Diameter | 2.642 mm (0.1040 in) |
| Cross-sectional area | 5.4822 mm² |
| Copper resistance | 3.1374 Ω/km (0.9563 Ω/1000 ft) |
Full SWG to mm chart (BS 3737)
| SWG | Diameter (mm) | Diameter (in) | Area (mm²) |
|---|
How to Use the SWG to mm Calculator
Pick an SWG size from the list and the diameter, cross-sectional area and copper resistance appear instantly — or switch to millimetres mode, type a measured diameter, and the nearest SWG size is shown. The "Use" button on any row of the full chart loads that size into the calculator with one click, and the copy button puts the result ("12 SWG = 2.642 mm") on the clipboard. SWG sizes do not follow a formula the way AWG does: the diameters are a fixed table from the British standard BS 3737, so every value here is a lookup, not a calculation — which is exactly why a converter is useful.
The calculator covers all 57 SWG sizes, from 7/0 (the thickest, 12.7 mm) down to 50 (the thinnest, 0.025 mm). For each size it gives the diameter in millimetres and inches, the cross-sectional area in square millimetres, and the copper resistance per kilometre and per 1,000 feet at 20 °C.
SWG to mm Formulas
There is no formula for the SWG diameter itself — the table is the standard. Everything else follows from the diameter with ordinary geometry and the resistivity of copper.
The resistance constants come from copper's resistivity of 1.72 × 10⁻⁸ ohm-metres: a 1 km length of wire with area A mm² has resistance 17.2 ÷ A ohms, and 1,000 feet (304.8 m) has 5.2426 ÷ A ohms. The popular AWG system does have a diameter formula (0.005 × 92^((36 − n) ÷ 39) inches), but applying it to SWG gives wrong answers — the two systems use different steps, so always use the SWG table for SWG sizes.
Worked Example: 12 SWG and a Measured 2.5 mm Wire
Example — Lookup and reverse lookup
A drawing calls for 12 SWG copper wire for a 100 m run, and a spool in the workshop measures 2.5 mm across the bare conductor. Find the 12 SWG diameter, area and resistance, and identify the spool.
Step 1: From the table, 12 SWG = 2.642 mm diameter (0.104 in).
Step 2: Area: (π ÷ 4) × 2.642² = 5.4805 mm².
Step 3: Resistance per km: 17.2 ÷ 5.4805 = 3.139 Ω/km, so 100 m is 0.314 Ω.
Step 4: The spool at 2.5 mm sits between 12 SWG (2.642 mm) and 13 SWG (2.337 mm); it is closer to 12 SWG (0.142 mm away versus 0.163 mm), so it is nearest to 12 SWG.
The reverse lookup is a nearest match, not an exact one: a measured 2.5 mm wire is not exactly any SWG size, and the honest answer is "nearest to 12 SWG". If the application needs the exact diameter, quote the millimetres, not the gauge.
Common SWG to mm Conversions
| SWG | Diameter (mm) | Diameter (in) | Area (mm²) |
|---|---|---|---|
| 7/0 | 12.700 | 0.5000 | 126.677 |
| 4/0 | 10.160 | 0.4000 | 81.073 |
| 0 | 8.230 | 0.3240 | 53.192 |
| 4 | 5.893 | 0.2320 | 27.273 |
| 8 | 4.064 | 0.1600 | 12.972 |
| 10 | 3.251 | 0.1280 | 8.302 |
| 12 | 2.642 | 0.1040 | 5.481 |
| 14 | 2.032 | 0.0800 | 3.243 |
| 16 | 1.626 | 0.0640 | 2.076 |
| 18 | 1.219 | 0.0480 | 1.168 |
| 20 | 0.914 | 0.0360 | 0.657 |
| 24 | 0.559 | 0.0220 | 0.245 |
| 30 | 0.315 | 0.0124 | 0.078 |
| 40 | 0.122 | 0.0048 | 0.012 |
| 50 | 0.025 | 0.0010 | 0.0005 |
SWG, AWG and BWG: Three Gauges That Disagree
The same gauge number means different diameters in different systems — that is the trap this calculator exists to avoid. 12 SWG is 2.642 mm; 12 AWG is 2.053 mm; 12 BWG (Birmingham Wire Gauge, used for sheet metal and tubes) is 2.769 mm. Ordering "12 gauge" without naming the system can deliver wire 30% too thin or too thick, and in a mains circuit the thin option is a fire risk. Always quote the millimetre diameter alongside the gauge, and never convert between SWG and AWG with a formula — match the diameters in the two tables instead.
SWG is a British imperial system, standardised as BS 3737 and now withdrawn in favour of metric sizes, but it still appears on old drawings, in restoration work and in Commonwealth countries. The numbering runs backwards like AWG: a bigger number is a thinner wire, because the number originally counted how many times the wire had been drawn through the dies. The 7/0 sizes (pronounced "seven-aught") are the thickest; 50 is finer than a human hair.
Common Mistakes When Converting SWG to mm
- Using the AWG formula for SWG. The AWG diameter formula gives 2.053 mm for "12 gauge" — the AWG value, not the SWG value of 2.642 mm. SWG has no formula; use the table.
- Assuming bigger gauge means bigger wire. It is the opposite: 20 SWG (0.914 mm) is far thinner than 10 SWG (3.251 mm). The backward numbering catches everyone once.
- Measuring over the insulation. Insulation adds a millimetre or more. Strip the wire and measure the bare conductor with calipers, in two or three places, and average the readings.
- Treating a nearest match as exact. A measured 2.5 mm wire is nearest to 12 SWG, but it is not 12 SWG — it is 2.5 mm wire. For ordering and for current ratings, the millimetres are the truth.
- Forgetting resistance rises with temperature. The table values are at 20 °C. Copper resistance rises about 0.4% per degree, so a wire at 70 °C has about 20% more resistance than the table says.
- Mixing SWG with sheet-metal gauge. SWG is also used for sheet thickness, but the wire table and the sheet table are the same numbers only by convention — verify which one a drawing means before ordering.
Three anchors cover most lookups: 10 SWG is 3.251 mm, 12 SWG is 2.642 mm, and 20 SWG is 0.914 mm. Household wiring is typically 1.5–2.5 mm² (roughly 15–13 SWG), and the jump from 12 SWG to 14 SWG nearly halves the area — numbers that make the scale of the gauge concrete before converting.
My saved numbers reuse them in any calculator
Save a number once — like your rent or hourly rate — then just type its name instead of the number, in any calculator here. You can also type formulas like 5000 * 1.1 right into any box.
Saved only in this browser — nothing is sent to us.
Frequently Asked Questions
What is SWG?
SWG — Standard Wire Gauge, also called British Standard Wire Gauge — is the imperial system for wire diameters used in Britain and the Commonwealth, standardised as BS 3737. It covers solid round wire from 7/0 (12.7 mm) down to 50 (0.025 mm). It is now withdrawn in favour of metric sizes but still appears on old drawings and in restoration work.
Does a bigger SWG number mean a bigger wire?
The opposite: a bigger number means a thinner wire. 7/0 is the thickest, 50 is the thinnest. Each step changes the diameter by a fixed amount within a range, and the number originally counted how many times the wire had been drawn through the dies.
How is SWG different from AWG?
They are different systems with different diameters for the same number: 12 SWG is 2.642 mm, 12 AWG is 2.053 mm, and 12 BWG is 2.769 mm. There is no formula linking them — match the diameters in the two tables. Always quote millimetres alongside the gauge.
Why is there no formula for SWG to mm?
Unlike AWG, whose diameters follow one formula, SWG diameters are a fixed table with steps that change between gauge ranges. The only exact conversion is a lookup in the BS 3737 table — which is what this calculator does.
How do I measure a wire to find its SWG size?
Strip the insulation and measure the bare conductor with calipers — in millimetres is easiest. Measure in two or three places and take the average, since wire is rarely perfectly round. Then enter the diameter in millimetres mode: the nearest SWG size is shown. Do not measure over the insulation.
How is the copper resistance worked out?
From the area and copper resistivity (1.72 × 10⁻⁸ ohm-m at 20 °C): resistance per km is 17.2 ÷ area in mm², and per 1,000 ft it is 5.2426 ÷ area. Resistance rises about 0.4% per degree above 20 °C, so a wire at 70 °C has about 20% more resistance than the table value.
What is the area of 12 SWG wire?
12 SWG is 2.642 mm across, so its area is (π ÷ 4) × 2.642² = 5.4805 mm². Its copper resistance is 3.139 Ω/km, or 0.955 Ω per 1,000 ft.